USER’S GUIDE
Switched Rack PDU
38
How to create multiple global outlet groups (Web interface)
To set up multiple global outlet groups that link to outlet groups on other
Switched Rack PDUs:
1. From the Outlets menu in the Web interface, select Outlet Groups.
2. Make sure outlet groups are enabled and that the Multicast parameters
(name and IP address) are the same for all Rack PDUs to be linked.
3. Click Create Global Outlet Groups.
4. For each global outlet group you want to create, select an outlet by
clicking on its check-box. Then click Apply. For example, select five
outlets to create five outlet groups, each consisting of one global outlet.
5. To add outlets to any of the global outlet groups you created, see How
to edit or delete an outlet group.
How to edit or delete an outlet group
1. From the Outlets menu in the Web interface, select Outlet Groups.
2. Under Configured Outlet Groups, click on the number or name of the
outlet group to edit or delete.
3. When editing an outlet group you can do any of the following:
Rename the outlet group.
Add or remove outlets by clicking the check-boxes to mark or
unmark them.
4. To delete the outlet group, click Delete Outlet Group.
See How to enable outlet groups.
You cannot remove an outlet from an outlet group that
contains only two outlets unless the remaining outlet is a
global outlet.